R-32 PT chart

R-32 reads 121.0 psig at 40°F and 325.7 psig at 100°F, slightly above R-410A at the same temperatures.

R-32 lookup

–Enter a value.

R-32 at a glance

Safety group
A2L
Type
HFC, single component
Composition
Difluoromethane (CH2F2), 100 %
GWP (100-yr)
675 (AR4) · 677 (AR5)
Lubricant
POE
Boiling point
-61.0°F at 1 atm
Critical temperature
172.6°F
Used in
Residential and commercial air conditioning; Heat pumps; Dehumidifiers; Small chillers
Replaces
R-410A
Also sold as
HFC-32, Forane 32

EPA lists R-32 as acceptable, subject to use conditions, in new residential and light commercial AC and heat pumps under its SNAP program. Its AR4 GWP of 675 is under the 700 limit that EPA's Technology Transitions rule applies to that equipment from January 1, 2025.

R-32 pressure-temperature table

Every 5°F shown. ″ Hg = inches of mercury vacuum.
R-32 saturation pressure, psig at sea level
°F°Cpsig
-40-40.011.0
-39-39.411.7
-38-38.912.4
-37-38.313.0
-36-37.813.7
-35-37.214.4
-34-36.715.2
-33-36.115.9
-32-35.616.6
-31-35.017.4
-30-34.418.2
-29-33.919.0
-28-33.319.8
-27-32.820.6
-26-32.221.4
-25-31.722.3
-24-31.123.2
-23-30.624.1
-22-30.025.0
-21-29.425.9
-20-28.926.8
-19-28.327.8
-18-27.828.7
-17-27.229.7
-16-26.730.7
-15-26.131.7
-14-25.632.8
-13-25.033.8
-12-24.434.9
-11-23.936.0
-10-23.337.1
-9-22.838.2
-8-22.239.4
-7-21.740.5
-6-21.141.7
-5-20.642.9
-4-20.044.1
-3-19.445.4
-2-18.946.7
-1-18.348.0
0-17.849.3
1-17.250.6
2-16.751.9
3-16.153.3
4-15.654.7
5-15.056.1
6-14.457.5
7-13.959.0
8-13.360.5
9-12.862.0
10-12.263.5
11-11.765.0
12-11.166.6
13-10.668.2
14-10.069.8
15-9.471.5
16-8.973.1
17-8.374.8
18-7.876.5
19-7.278.3
20-6.780.0
21-6.181.8
22-5.683.6
23-5.085.5
24-4.487.3
25-3.989.2
26-3.391.1
27-2.893.1
28-2.295.1
29-1.797.1
30-1.199.1
31-0.6101.2
320.0103.2
330.6105.3
341.1107.5
351.7109.7
362.2111.9
372.8114.1
383.3116.3
393.9118.6
404.4121.0
415.0123.3
425.6125.7
436.1128.1
446.7130.5
457.2133.0
467.8135.5
478.3138.0
488.9140.6
499.4143.2
5010.0145.8
5110.6148.5
5211.1151.2
5311.7153.9
5412.2156.7
5512.8159.5
5613.3162.3
5713.9165.2
5814.4168.1
5915.0171.1
6015.6174.1
6116.1177.1
6216.7180.1
6317.2183.2
6417.8186.3
6518.3189.5
6618.9192.7
6719.4195.9
6820.0199.2
6920.6202.5
7021.1205.8
7121.7209.2
7222.2212.6
7322.8216.1
7423.3219.6
7523.9223.2
7624.4226.7
7725.0230.4
7825.6234.0
7926.1237.7
8026.7241.5
8127.2245.3
8227.8249.1
8328.3253.0
8428.9256.9
8529.4260.9
8630.0264.9
8730.6268.9
8831.1273.0
8931.7277.1
9032.2281.3
9132.8285.6
9233.3289.8
9333.9294.1
9434.4298.5
9535.0302.9
9635.6307.4
9736.1311.9
9836.7316.4
9937.2321.0
10037.8325.7
10138.3330.4
10238.9335.1
10339.4339.9
10440.0344.8
10540.6349.6
10641.1354.6
10741.7359.6
10842.2364.6
10942.8369.7
11043.3374.9
11143.9380.1
11244.4385.3
11345.0390.6
11445.6396.0
11546.1401.4
11646.7406.9
11747.2412.4
11847.8418.0
11948.3423.6
12048.9429.3
12149.4435.1
12250.0440.9
12350.6446.8
12451.1452.7
12551.7458.7
12652.2464.7
12752.8470.8
12853.3477.0
12953.9483.2
13054.4489.5
13155.0495.8
13255.6502.2
13356.1508.7
13456.7515.2
13557.2521.8
13657.8528.5
13758.3535.2
13858.9542.0
13959.4548.9
14060.0555.8
14160.6562.8
14261.1569.8
14361.7577.0
14462.2584.1
14562.8591.4
14663.3598.7
14763.9606.1
14864.4613.6
14965.0621.2
15065.6628.8
15166.1636.5
15266.7644.3
15367.2652.2
15467.8660.1
15568.3668.1
15668.9676.2
15769.4684.4
15870.0692.6
15970.6701.0
16071.1709.4

Saturation pressures computed with CoolProp 8.0.0 (R32) on October 10, 2026, gauge pressure at sea level. Checked against Arkema published chart at 8 points; largest difference 0.05 psi. How these numbers are made.

What R-32 is and where it is used

R-32 is difluoromethane, a single-component HFC. It is half of R-410A by weight and 68.9% of R-454B. Arkema says it was developed to replace R-410A in many air conditioning applications, and lists new residential and commercial air conditioners, heat pumps, dehumidifiers and small chillers as its uses. Its 100-year GWP is 675 (AR4) or 677 (AR5), about a third of R-410A's 2088.

R-32 is ASHRAE safety group A2L: lower toxicity and mild flammability. Arkema says that because of its mild flammability and higher operating pressures, R-32 should never be used to retrofit an existing R-410A system. Read what A2L refrigerants change for techs before working on it.

How to read the R-32 chart

R-32 is a single compound, so the bubble and dew pressures are the same and the chart has one pressure per temperature. Use the same column for superheat and subcooling.

  • Superheat: a suction reading of 121 psig converts to 40.0°F. Subtract that from the suction line temperature.
  • Subcooling: a liquid line reading of 400 psig converts to 114.7°F. Subtract the liquid line temperature from it.

R-32 boils at -61.0°F at atmospheric pressure, so it stays above 0 psig across the whole chart. Its critical temperature is 172.6°F. The superheat calculator and subcooling calculator do the conversion, and how to read a PT chart covers the method.

Example R-32 pressures on an air conditioner

The figures below are worked examples at assumed coil temperatures, not targets for any unit:

  • Suction: at a 40°F evaporator saturation temperature, R-32 reads about 121.0 psig, compared with 118.4 psig for R-410A.
  • Head: at 115°F and 125°F condensing temperatures, R-32 reads 401.4 psig and 458.7 psig. R-410A would read 392.3 psig and 448.0 psig.

Arkema puts typical R-32 operating pressures 5 to 10% above R-410A at comparable conditions. It tells users to check the equipment manufacturer's guidelines for charging instructions, so charge to the method and values in the installation manual.

Service notes

  • Oil: Arkema says R-32 is typically used with POE oil, since it does not mix with mineral oil or alkylbenzene. It warns that POE is hygroscopic and readily absorbs moisture from the air, and that high moisture levels can lead to oil degradation and system failure.
  • Charging: R-32 is a single compound, and Arkema says it can be charged as vapor or liquid. Follow the manufacturer's instructions.
  • Discharge temperature: Arkema notes R-32 runs higher discharge temperatures than R-410A, which the equipment design must accommodate. It also has a higher volumetric capacity than R-410A and needs a smaller charge.
  • Tools: Chemours says some service equipment, because of its electrical components and motors, should be designed for mildly flammable A2L refrigerants such as R-32. Its A2L tool list calls for 2L-certified recovery machines and leak detectors and recovery cylinders labeled flammable with left-hand threads.

R-32 among the R-410A replacements

EPA's Technology Transitions rule set a GWP limit of 700 for new residential and light commercial AC and heat pumps from January 1, 2025. R-32 (675) and R-454B (465) both meet it, and EPA lists both under SNAP for that equipment. At 40°F, R-32 reads 121.0 psig, R-410A dew reads 118.4 psig and R-454B dew reads 107.0 psig. Chemours says not to mix refrigerants, so charge only the refrigerant on the unit's nameplate. Compare them in R-410A vs R-32 and R-454B vs R-32.

Last reviewed October 10, 2026.

Sources

  1. Arkema, Forane refrigerants pressure-temperature chart (R-32)
  2. Arkema, Forane Refrigerants Technical Digest (Forane 32: applications, A2L, retrofit warning, pressures, discharge temperature, lubricant, charging, AR5 GWP)
  3. Chemours, Pressure-Temperature Guide for A/C (R-32 safety group A2L; do not mix refrigerants)
  4. EPA, Technology Transitions GWP reference table (HFC-32, R-410A, R-454B)
  5. EPA, SNAP substitutes in residential and light commercial air conditioning and heat pumps (HFC-32 and R-454B listings)
  6. EPA, Technology Transitions HFC restrictions by sector
  7. Chemours, Safety of Opteon XL refrigerants (A2L service equipment)
  8. ASHRAE, Refrigerant designations (R-32 name and formula; R-410A and R-454B compositions)
  9. Arkema PT chart (used to validate this table)
  10. Bell, Wronski, Quoilin, Lemort: Pure and Pseudo-pure Fluid Thermophysical Property Evaluation and the Open-Source Thermophysical Property Library CoolProp (Ind. Eng. Chem. Res., 2014)