R-507A PT chart

R-507A reads 17.6 psig at -20°F, 89.3 psig at 40°F and 242.3 psig at 100°F.

R-507A lookup

–Enter a value.

R-507A at a glance

Safety group
A1
Type
HFC blend, azeotropic
Composition
R-125 / R-143a, 50 / 50 % by weight
GWP (100-yr)
3985 (AR4) · 3985 (AR5)
Lubricant
POE
Boiling point
-52.1°F at 1 atm
Critical temperature
159.1°F
Used in
Low- and medium-temperature commercial refrigeration: supermarket rack systems and condensing units; Transport refrigeration; Replacement for R-502
Replaced by
R-449A, R-448A
Also sold as
Genetron AZ-50, Freon 507

With a GWP of 3,985, R-507A is above every EPA Technology Transitions limit for new refrigeration equipment: stand-alone units (150, since Jan 1, 2025), remote condensing units and cold storage warehouses (from July 27, 2026) and supermarket systems (from Jan 1, 2027). Existing systems may still be serviced, while the AIM Act phasedown cuts allowed HFC production and consumption to 30% of baseline from 2029.

R-507A pressure-temperature table

Every 5°F shown. ″ Hg = inches of mercury vacuum.
R-507A saturation pressure, psig at sea level
°F°Cpsig
-40-40.05.4
-39-39.45.9
-38-38.96.4
-37-38.37.0
-36-37.87.5
-35-37.28.1
-34-36.78.6
-33-36.19.2
-32-35.69.8
-31-35.010.3
-30-34.411.0
-29-33.911.6
-28-33.312.2
-27-32.812.8
-26-32.213.5
-25-31.714.1
-24-31.114.8
-23-30.615.5
-22-30.016.2
-21-29.416.9
-20-28.917.6
-19-28.318.3
-18-27.819.1
-17-27.219.8
-16-26.720.6
-15-26.121.4
-14-25.622.2
-13-25.023.0
-12-24.423.8
-11-23.924.7
-10-23.325.5
-9-22.826.4
-8-22.227.3
-7-21.728.1
-6-21.129.1
-5-20.630.0
-4-20.030.9
-3-19.431.9
-2-18.932.8
-1-18.333.8
0-17.834.8
1-17.235.8
2-16.736.9
3-16.137.9
4-15.639.0
5-15.040.0
6-14.441.1
7-13.942.3
8-13.343.4
9-12.844.5
10-12.245.7
11-11.746.9
12-11.148.1
13-10.649.3
14-10.050.5
15-9.451.8
16-8.953.0
17-8.354.3
18-7.855.6
19-7.256.9
20-6.758.3
21-6.159.6
22-5.661.0
23-5.062.4
24-4.463.8
25-3.965.3
26-3.366.7
27-2.868.2
28-2.269.7
29-1.771.2
30-1.172.7
31-0.674.3
320.075.9
330.677.5
341.179.1
351.780.7
362.282.4
372.884.1
383.385.8
393.987.5
404.489.3
415.091.0
425.692.8
436.194.6
446.796.5
457.298.3
467.8100.2
478.3102.1
488.9104.1
499.4106.0
5010.0108.0
5110.6110.0
5211.1112.0
5311.7114.1
5412.2116.2
5512.8118.3
5613.3120.4
5713.9122.6
5814.4124.8
5915.0127.0
6015.6129.2
6116.1131.4
6216.7133.7
6317.2136.0
6417.8138.4
6518.3140.8
6618.9143.1
6719.4145.6
6820.0148.0
6920.6150.5
7021.1153.0
7121.7155.5
7222.2158.1
7322.8160.7
7423.3163.3
7523.9165.9
7624.4168.6
7725.0171.3
7825.6174.1
7926.1176.8
8026.7179.6
8127.2182.4
8227.8185.3
8328.3188.2
8428.9191.1
8529.4194.1
8630.0197.1
8730.6200.1
8831.1203.1
8931.7206.2
9032.2209.3
9132.8212.4
9233.3215.6
9333.9218.8
9434.4222.1
9535.0225.4
9635.6228.7
9736.1232.0
9836.7235.4
9937.2238.8
10037.8242.3
10138.3245.8
10238.9249.3
10339.4252.9
10440.0256.4
10540.6260.1
10641.1263.8
10741.7267.5
10842.2271.2
10942.8275.0
11043.3278.8
11143.9282.7
11244.4286.6
11345.0290.5
11445.6294.5
11546.1298.5
11646.7302.6
11747.2306.7
11847.8310.8
11948.3315.0
12048.9319.2
12149.4323.5
12250.0327.8
12350.6332.1
12451.1336.5
12551.7340.9
12652.2345.4
12752.8349.9
12853.3354.5
12953.9359.1
13054.4363.8
13155.0368.5
13255.6373.2
13356.1378.0
13456.7382.9
13557.2387.8
13657.8392.7
13758.3397.7
13858.9402.8
13959.4407.9
14060.0413.0
14160.6418.2
14261.1423.4
14361.7428.8
14462.2434.1
14562.8439.5
14663.3445.0
14763.9450.5
14864.4456.1
14965.0461.8
15065.6467.5
15166.1473.2
15266.7479.1
15367.2485.0
15467.8490.9
15568.3497.0
15668.9503.1
15769.4509.3
15870.0515.6

Saturation pressures computed with CoolProp 8.0.0 (R507A) on October 10, 2026, gauge pressure at sea level. Checked against Honeywell published chart at 8 points; largest difference 0.04 psi. How these numbers are made.

What R-507A is and where it is used

R-507A is a 50/50 blend of R-125 and R-143a by weight. Honeywell sold it as Genetron AZ-50, and Chemours sells it as Freon 507. It is an azeotrope, so it boils and condenses at one temperature for a given pressure, like a single-component refrigerant. It carries an ASHRAE A1 rating.

Chemours describes R-507A as a zero-ODP HFC and a long-term replacement for R-502 that works over the entire R-502 operating range, in commercial refrigeration such as supermarket and transport systems. EPA lists R-507A, along with R-404A and R-407A, among the refrigerants most often found in supermarket rack systems, and also in some condensing units.

How to read the R-507A chart

Because R-507A is azeotropic, its bubble and dew pressures are effectively the same, so the chart shows one column. In the computed table the two values differ by a few tenths of a psi at most, too little to change a superheat or subcooling reading. Use the same column for both readings:

  • Superheat: at 50 psig suction the saturation temperature is 13.6°F. Subtract it from the suction line temperature, or use the superheat calculator.
  • Subcooling: at 250 psig liquid pressure the saturation temperature is 102.2°F. Subtract the liquid line temperature, or use the subcooling calculator.

Do not swap in an R-404A chart. The two are close but not identical: at 40°F, R-507A is 89.3 psig and R-404A is 86.9 psig bubble. See how to read a PT chart.

Typical R-507A pressures

Chemours' R-404A/R-507 retrofit guide compares refrigerants at a 104°F condensing temperature, a 14°F medium-temperature evaporator and a -22°F low-temperature evaporator. At those saturation temperatures R-507A reads:

  • Low-temperature suction at -22°F: 16.2 psig
  • Medium-temperature suction at 14°F: 50.5 psig
  • Condensing at 104°F: 256.4 psig

These are saturation pressures at the stated temperatures, not service targets. Check the equipment's installation manual for operating pressures and set points.

Service notes

  • Oil. Chemours says equipment makers recommend POE with R-507A. Arkema rates both of its components, R-125 and R-143a, as poorly soluble in mineral oil and alkylbenzene.
  • Charging. Arkema notes that fractionation from leaks is small with an azeotrope, and Chemours says R-507A does not separate when it leaks. Arkema still advises charging all blends as liquid.
  • Flammability. Arkema lists R-143a alone as A2L (mildly flammable), but the R-507A blend is rated A1. Chemours warns that no HFC-containing blend should be mixed with air to check for leaks. Pressure test with dry nitrogen.
  • Converting. Chemours publishes a procedure for moving R-507 systems to R-449A, keeping the existing POE in most systems. Suction pressure changes: at a 14°F saturation temperature R-507A reads 50.5 psig and R-449A reads 37.6 psig dew. Chemours says set points and cutouts may need resetting.

Status and replacements

R-507A's GWP of 3,985 is far above EPA's Technology Transitions limits for new equipment. New stand-alone units have been capped at 150 since 2025. The current limits also bar it from new remote condensing units and cold storage warehouses installed from July 27, 2026, and from new supermarket systems installed from Jan 1, 2027. EPA says existing systems may be serviced and repaired throughout their useful life. HFC supply is limited by the AIM Act phasedown, which drops allowed production and consumption to 30% of the historic baseline in 2029. Chemours (R-449A) and Honeywell (R-448A) both market blends to replace R-507 in low- and medium-temperature systems, new or retrofit. EPA lists R-744 (CO2) as acceptable in retail food refrigeration, and transcritical CO2 racks are in use in US supermarkets.

Last reviewed October 10, 2026.

Sources

  1. Honeywell, Genetron refrigerants pressure-temperature chart (AZ-50 properties and lubricant), hosted by RSD
  2. Chemours, Freon 507 (R-507) product page (Wayback Machine copy, May 2025)
  3. ASHRAE, Refrigerant designations (R-507A azeotrope composition)
  4. Honeywell, Solstice N40 (R-448A) technical data sheet (replacement for R-404A/R-507)
  5. EPA, Transitioning to low-GWP alternatives in commercial refrigeration (2016)
  6. Arkema (EPA-hosted), Choosing the Right R-22 Retrofit: blend compositions and charging
  7. Hudson Technologies, R-507 pressure-temperature chart and properties
  8. Chemours, Opteon XP40 retrofit guidelines to replace R-404A/R-507
  9. California Air Resources Board, High-GWP refrigerants (AR4 and AR5 values)
  10. EPA, Technology Transitions GWP reference table
  11. EPA, Technology Transitions HFC restrictions by sector
  12. EPA, Technology Transitions program fact sheet (HFC phasedown schedule, maintenance of existing systems)
  13. EPA, SNAP substitutes in household refrigerators and freezers (R-507A AZ-50: safety class A1)
  14. Bell, Wronski, Quoilin, Lemort: Pure and Pseudo-pure Fluid Thermophysical Property Evaluation and the Open-Source Thermophysical Property Library CoolProp (Ind. Eng. Chem. Res., 2014)