Wire gauge chart (AWG)

12 AWG copper is 0.0808 in (2.05 mm) across with an area of 6,529 circular mils (3.31 mm²), and measures 1.589 ohms per 1,000 ft at 20°C; 12 AWG aluminum measures 2.604 ohms.

AWG wire gauge chart: diameter, area and DC resistance of copper and aluminum

AWG sizes, solid round wire (ASTM B258 diameters)
AWG / kcmilDiameter (in)Diameter (mm)Area (circular mils)Area (mm²)Copper, ohms per 1,000 ft at 20°C (ohm/1000 ft)Copper, ohms per km at 20°C (ohm/km)Aluminum, ohms per 1,000 ft at 20°C (ohm/1000 ft)Aluminum, ohms per km at 20°C (ohm/km)
4/00.460011.684211600107.20.049010.16080.080350.2636
3/00.409610.40416780085.010.061820.20280.10130.3325
2/00.36489.26613310067.430.077930.25570.12780.4192
1/00.32498.25210560053.490.098250.32230.16110.5284
10.28937.3488369042.410.12390.40660.20310.6665
20.25766.5436636033.620.15630.51280.25620.8406
30.22945.8275262026.670.19710.64660.32311.06
40.20435.1894174021.150.24850.81520.40731.336
50.18194.6203309016.770.31341.0280.51381.686
60.16204.1152624013.30.39521.2970.64782.125
70.14433.6652082010.550.49811.6340.81652.679
80.12853.264165108.3670.62812.0611.033.378
90.11442.906130906.6310.79252.61.2994.262
100.10192.588103805.2610.99883.2771.6375.372
110.09072.30482264.1681.2614.1362.0676.781
120.08082.05265293.3081.5895.2122.6048.544
130.07201.82951842.6272.0016.5643.2810.76
140.06411.62841092.0822.5248.2814.13813.58
150.05711.45032601.6523.18110.445.21517.11
160.05081.29025811.3084.01913.196.58821.62
170.04531.15120521.045.05416.588.28527.18
180.04031.02416240.82296.38620.9510.4734.35
190.03590.91212890.6538.04726.413.1943.28
200.03200.81310240.518910.1333.2316.654.47
210.02850.724812.30.411612.7741.8920.9368.67
220.02530.643640.10.324316.253.1626.5687.15
230.02260.574510.80.258820.3166.6233.29109.2
240.02010.5114040.204725.6784.2242.08138.1
250.01790.455320.40.162432.37106.253.06174.1
260.01590.404252.80.128141.02134.667.25220.6
270.01420.361201.60.102251.43168.784.32276.6
280.01260.320158.80.0804465.33214.3107.1351.4
290.01130.287127.70.064781.22266.5133.2436.8
300.01000.2541000.05067103.7340.3170557.8
310.00890.22679.210.04014130.9429.6214.6704.2
320.00800.203640.03243162.1531.7265.7871.6
330.00710.18050.410.02554205.7675337.31107
340.00630.16039.690.02011261.3857.3428.41405
350.00560.14231.360.01589330.71085542.21779
360.00500.127250.01267414.81361680.12231
370.00450.11420.250.01026512.21680839.62755
380.00400.102160.008107648.2212710633486
390.00350.08912.250.006207846.6277813884554
400.00310.0799.610.0048691079354117695804
kcmil sizes, Class B concentric stranded copper and aluminum
AWG / kcmilDiameter (in)Diameter (mm)Stranded OD, Class B (in)Stranded OD, Class B (mm)Area (circular mils)Area (mm²)Copper, ohms per 1,000 ft at 20°C (ohm/1000 ft)Copper, ohms per km at 20°C (ohm/km)Aluminum, ohms per 1,000 ft at 20°C (ohm/1000 ft)Aluminum, ohms per km at 20°C (ohm/km)
250 kcmil0.500012.7000.57514.61250000126.70.042310.13880.069370.2276
300 kcmil0.547713.9120.63016.003000001520.035260.11570.057810.1897
350 kcmil0.591615.0270.68117.30350000177.30.030220.099160.049550.1626
400 kcmil0.632516.0640.72818.49400000202.70.026450.086770.043360.1422
500 kcmil0.707117.9610.81320.65500000253.40.021160.069410.034680.1138

Diameters are ASTM B258 nominal values: the AWG formula rounded to the nearest 0.1 mil (0.0001 in), as NBS Handbook 100 describes. Areas and resistances are computed from those rounded diameters, the same way NBS Handbook 100 does it.

Resistance is DC resistance of solid annealed copper at 100% IACS (NBS Handbook 100) and of aluminum 1350-H19 (EC-H19) at 61.0% IACS (NBS Handbook 109), both at 20°C (68°F). For another temperature T in °C multiply by 1 + 0.00393 (T - 20) for copper or 1 + 0.00403 (T - 20) for aluminum.

Stranded wire of the same AWG has the same nominal area but a larger diameter, and its resistance is higher because the strands spiral: NBS Handbook 100 uses 2% for sizes up to 2,000,000 circular mils. The kcmil rows are Class B concentric stranded (37 wires). Their Diameter column is the solid-equivalent diameter (the square root of the area in circular mils), the Stranded OD column is the diameter over the strands from NBS Handbook 100 Table 17, and the resistance includes that 2%.

MWS Wire Industries' EC aluminum table reads about 0.3% lower than this table (12 AWG: 2.596 against 2.604 ohms per 1,000 ft at 20°C); this table uses the 61.0% IACS value from NBS Handbook 109.

This table gives physical properties only. It does not give ampacity, the current a conductor can carry continuously under its conditions of use without exceeding its temperature rating; get that from the electrical code adopted where you work and the wire maker's data.

Cross-checked against National Bureau of Standards (now NIST), Handbook 100, Copper Wire Tables (1966), Tables 1, 5, 10 and 17 and MWS Wire Industries, Copper Magnet Wire Data (bare copper, 6 to 56 AWG) and Southwire, SPEC 80150 Bare Copper Wire and Cable, Solid and Stranded (rev. Jan 26, 2026) and MWS Wire Industries, Aluminum and Aluminum Alloys: EC (1350) Aluminum Wire Data and Southwire, AAC All Aluminum Conductor, Bare (ASTM B230/B231 1350-H19) specification: Copper: all 44 AWG rows (4/0 to 40) match Table 5 (diameter, circular mils, ohms per 1,000 ft) and Table 10 (mm², ohms per km) to the handbook's printed precision (it prints 20.25 and 12.25 cmil for 37 and 39 AWG as 20.2 and 12.2, and 1 AWG at 0.40655 ohms per km rounds to its 0.4065). One cell in the scanned text layer reads 1200 cmil for 19 AWG; the printed diameter, 35.9 mils, gives 1289, which MWS also lists, so it is a scan misread. kcmil: our stranded values corrected to 25°C match Table 17 for all five sizes.; Copper: all 35 rows from 6 to 40 AWG match MWS nominal bare diameter, circular mils and nominal resistance within 0.06%.; Copper: 14 solid sizes (14 to 1 AWG) match Southwire's soft-drawn diameter, area and 20°C resistance, except 13 AWG, where Southwire lists 2.003 against our 2.001 (MWS also lists 2.001). Stranded 4/0 to 1/0 and 250 to 500 kcmil equal our solid values times the 2% stranding increment (e.g. 250 kcmil 0.04231), and Class B diameters 575, 630, 681 match; Southwire lists 500 kcmil at 814 mils against Table 17's 813. Southwire's 3/0 19-wire row is marked as interpolated and was not used.; Aluminum: all 31 rows from 10 to 40 AWG run 0.31 to 0.37% above MWS. MWS values imply 61.2% IACS; this table uses the 61.0% value from NBS Handbook 109, the more conservative (higher) resistance.; Aluminum: 6 AWG to 4/0 and 250 to 500 kcmil stranded 1350-H19 resistance at 20°C runs 0.1 to 0.5% below our values times 1.02, consistent with Southwire's three-figure rounding and a 61.2% IACS basis..

How AWG sizes are defined

American Wire Gauge fixes two sizes and spaces the rest between them in a geometric progression: 36 AWG is 0.0050 in and 4/0 (0000) is 0.4600 in, with 38 sizes in between. ASTM B258 prescribes the nominal diameters. As NBS Handbook 100 describes it, each one is calculated as d = 0.005 in x 92(36 - n)/39 and rounded to the nearest 0.1 mil (0.0001 in). NBS notes that these rounded diameters are the ones used commercially, and every area and resistance in the chart is computed from them.

Because each step is the same ratio (1.1229 in diameter), NBS Handbook 100 lists a few shortcuts that hold across the whole range:

  • Every 3 gauges doubles the area and halves the resistance: 10 AWG is 10,380 circular mils, 13 AWG is 5,184.
  • Every 6 gauges doubles the diameter: 12 AWG is 0.0808 in, 18 AWG is 0.0403 in.
  • Every 10 gauges multiplies the area by about 10: 20 AWG is 1,024 circular mils, 10 AWG is 10,380.

NBS Handbook 100 notes that conductors larger than 4/0 are generally named by their area in circular mils. In kcmil (thousands of circular mils), a 250 kcmil conductor has 250,000 circular mils, or 126.7 mm².

Reading the columns

  • Diameter is the bare solid wire, in inches and millimeters. Stranded wire of the same gauge has the same metal area but a larger outside diameter. The kcmil rows give two diameters: a solid rod of the same area, and the outside of a standard concentric (ASTM Class B) 37-wire stranded conductor from NBS Handbook 100, Table 17. 250 kcmil is 0.500 in as a solid rod and 0.575 in stranded.
  • Area in circular mils is the diameter in mils squared: 12 AWG is 80.8 x 80.8 = 6,529. It is the CM in the voltage drop formula.
  • Area in mm² is the true cross-section. One circular mil is 0.0005067 mm². See the AWG to mm² converter for metric cable sizes.
  • Resistance is DC resistance at 20°C (68°F), per 1,000 ft and per km, for annealed copper at the international standard (10.371 ohm-cmil/ft, NBS Handbook 100) and for aluminum 1350-H19 (EC-H19 in NBS Handbook 109) at 61.0% of copper's conductivity (17.002 ohm-cmil/ft). Resistance of a run is the per-1,000-ft value times the total wire length in thousands of feet: 200 ft of 12 AWG copper (100 ft out and back) is 0.318 ohms.

Copper vs aluminum

At 61.0% of copper's conductivity, aluminum 1350 has 1.64 times the resistance of copper at the same size. NBS Handbook 100 gives 1.2610 as the area ratio from one gauge to the next, so going up two gauges adds about 59% more area, and aluminum two sizes larger comes close to copper: 4 AWG aluminum measures 0.4073 ohms per 1,000 ft against 0.3952 for 6 AWG copper, and 2 AWG aluminum measures 0.2562 against 0.2485 for 4 AWG copper.

Manufacturer tables can read slightly lower. MWS Wire Industries, which identifies EC aluminum as alloy 1350, lists 12 AWG at 2.596 ohms per 1,000 ft at 20°C, about 0.3% below this chart's 2.604. The chart uses the 61.0% value from NBS Handbook 109, the higher resistance. Stranded conductors measure about 2% more than solid ones of the same size, because the strands spiral: NBS Handbook 100 uses 2% up to 2,000,000 circular mils and up to 5% above that. Southwire lists stranded 4/0 soft copper at 0.04999 ohms per 1,000 ft at 20°C; the chart's solid 4/0 is 0.04901, 2% less.

Temperature

NBS Handbooks 100 and 109 give resistance rising by about 0.393% per °C for copper and 0.403% per °C for aluminum, measured from 20°C. Multiply the chart value by 1 + 0.00393 x (T - 20) for copper. At 75°C, the temperature IAEI gives for the published voltage drop constants, copper reads 1.216 times the chart: 12 AWG goes from 1.589 to 1.932 ohms per 1,000 ft (NBS Handbook 100 prints 1.93 at 75°C). That rise, plus the 2% allowance for stranding, is why the voltage drop constant for copper is 12.9 rather than 10.4.

Why ampacity is not on this page

Cerrowire defines ampacity as the maximum current a conductor can carry continuously under specific operating conditions without exceeding its temperature limit. It is not a property of the metal alone. Cerrowire's published ampacities are based on the National Electrical Code (NFPA 70), and it notes that they do not include the temperature correction or ampacity adjustments that may also be required. FieldCharts does not reproduce the NEC ampacity tables.

To find ampacity, use the edition of the code adopted where you work; NFPA offers free read-only access to its codes online, though not every edition is available that way. Some manufacturers list ratings for their own products, and those ratings come with conditions: Southwire's bare copper specification gives its ampacities at a 75°C conductor temperature, 25°C ambient and 2 ft per second of wind in sun. For equipment, check the installation manual. Cerrowire also points to the local building inspector or a qualified electrician.

Last reviewed October 10, 2026.

Sources

  1. ASTM B258, Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors
  2. National Bureau of Standards, Handbook 100: Copper Wire Tables (1966)
  3. National Bureau of Standards, Handbook 109: Aluminum Wire Tables (1972)
  4. MWS Wire Industries, Copper Magnet Wire Data
  5. MWS Wire Industries, Aluminum and Aluminum Alloys: EC (1350) Aluminum Wire Data
  6. Southwire, SPEC 80150 Bare Copper Wire and Cable
  7. IAEI Magazine, Voltage Drop Calculations (Sept/Oct 2019)
  8. Cerrowire, Ampacity Charts
  9. NFPA, NFPA 70 (NEC) code development page
  10. NFPA, Free access to NFPA codes and standards