AWG to mm² converter

12 AWG is 3.31 mm² (2.05 mm diameter) and 10 AWG is 5.26 mm²; neither is a metric cable size, so the nearest IEC sizes are 2.5 or 4 mm² for 12 AWG and 4 or 6 mm² for 10 AWG.

AWG to mm² converter

–

How the conversion works

An AWG number stands for a diameter. ASTM B258 prescribes the nominal diameters; as NBS Handbook 100 describes them, each is d = 0.005 in x 92(36 - n)/39, rounded to 0.0001 in. The area in mm² follows from the diameter in mm:

mm² = 3.1416 / 4 x d², with d in mm.

For 12 AWG, d = 0.0808 in = 2.0523 mm, so the area is 0.7854 x 2.0523² = 3.308 mm². From circular mils it is one multiplication: 1 circular mil = 0.0005067 mm², so 6,529 cmil x 0.0005067 = 3.308 mm². For kcmil sizes, mm² = kcmil x 0.5067: 250 kcmil is 126.7 mm².

Diameter in mm and area in mm² are easy to mix up. A wire 2 mm in diameter is close to 12 AWG (2.05 mm, 3.31 mm²). A 2 mm² wire is close to 14 AWG (2.08 mm²), which is only 1.63 mm across.

Metric sizes are a different series

Metric cable follows IEC 60228, which specifies nominal cross-sections from 0.5 mm² to 3,500 mm² for the conductors of power cables and cords. Lapp's technical table, which follows DIN EN 60228, lists the sizes from 0.5 mm² up as 0.5, 0.75, 1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240 and 300 mm², with larger sizes beyond. None of these equals an AWG area in the chart, so a conversion always lands between two metric sizes.

IEC 60228 also includes resistance values, not just areas. Lapp's table lists 7.41 ohms per km at 20°C as the maximum for a plain copper 2.5 mm² stranded (class 2) conductor. A true 2.5 mm² of annealed copper at the international standard in NBS Handbook 100 would measure 6.90 ohms per km. The limit leaves room for a conductor that carries less effective copper than its name, so compare resistance as well as area when the difference matters.

AWG to the nearest metric size

AWGArea (mm²)Next smaller IECNext larger IEC
200.5190.50.75
180.8230.751
161.3111.5
142.081.52.5
123.312.54
105.2646
88.37610
613.31016
421.21625
233.62535
1/053.55070
2/067.45070
3/085.07095
4/0107.295120
250 kcmil126.7120150
500 kcmil253.4240300

Metric size to an AWG size that covers it

When a manual or drawing calls for a metric size, an AWG wire with at least that area has no more resistance in the same metal, because resistance falls in proportion to area:

IEC size (mm²)AWG with at least that area
0.7518 AWG (0.823 mm²)
116 AWG (1.31 mm²)
1.514 AWG (2.08 mm²)
2.512 AWG (3.31 mm²)
410 AWG (5.26 mm²)
68 AWG (8.37 mm²)
106 AWG (13.3 mm²)
164 AWG (21.2 mm²)
253 AWG (26.7 mm²)
351 AWG (42.4 mm²)
501/0 (53.5 mm²)
703/0 (85.0 mm²)
954/0 (107.2 mm²)
120250 kcmil (126.7 mm²)
150300 kcmil (152.0 mm²)
185400 kcmil (202.7 mm²)
240500 kcmil (253.4 mm²)

Through 4 AWG the table gives the even gauge. The odd gauge one step smaller also covers each of those sizes: 17 AWG (1.04 mm²) for 1 mm², 15 AWG (1.65 mm²) for 1.5, 13 AWG (2.63 mm²) for 2.5, 11 AWG (4.17 mm²) for 4, 9 AWG (6.63 mm²) for 6, 7 AWG (10.55 mm²) for 10 and 5 AWG (16.77 mm²) for 16. A 2/0 conductor (67.4 mm²) is just under 70 mm², which is why 70 maps to 3/0.

Before you substitute

  • Check that the terminals accept the conductor. The terminal or equipment instructions give the sizes they take.
  • Area is not ampacity. The current a wire may carry is not on this page; get it from the electrical code adopted where you work and the cable maker's data. The wire gauge chart explains why it is not listed here.
  • For long runs, check the drop with the voltage drop calculator. A larger size has proportionally lower resistance, so it cuts the drop in proportion to the added area.

Last reviewed October 10, 2026.

Sources

  1. IEC 60228:2023, Conductors of insulated cables (scope and nominal cross-sections)
  2. Lapp, Technical table T11: conductor resistances and strand structure (metric), per DIN EN 60228
  3. ASTM B258, Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors
  4. National Bureau of Standards, Handbook 100: Copper Wire Tables (1966)
  5. National Bureau of Standards (now NIST), Handbook 109, Aluminum Wire Tables (1972), Table 1 (Aluminum 1350 (EC-H19), 61.0% IACS: 0.028264 ohm-mm²/m = 17.002 ohm-cmil/ft at 20°C, temperature coefficient 0.00403 per °C (Table 1).)